ZoneTeq Specifications & Performance


Manufacturer: Netfloor, Inc.

Module Set
500 mm x 500 mm
System height: 75 mm ~ 200 mm
System weight: avg. 36 ~ 38 kg / per sq. meter
Main Components
Power Distribution Box ZP401:
Size: 13.54” X 13.54” X 1.57” (344 mm X 344 mm X 40 mm)
Terminal block: 8 ports * 2
Conductor: 12 AWG copper wire
Box case
2.0 mm thick galvanized steel, inside the case 5 steel post support box cover.
Box cover: 3.0 mm thick galvanized steel.
10-pole whip: two whips at 2 sides of Box. Consists of 10*12 AWG wire
3/4” galvanized steel conduit, male connector as head to receive power, female connector as tail of the box.
3-pole whip: four whips at 2 other sides of Box. Consists of 3*12 AWG wire, 9/16”
galvanized steel conduit. All female connectors.

Power Entry (ZPJ-10PFE): 10*12 AWG wire, 4 hot, 4 neutral, 2 earth. Free wires at one end,
15 cm long other end protected by 3/4” galvanized steel conduit, male connector.

10-pole extenders: 10*12 AWG wire, 4 hot, 4 neutral, 2 earth, 3/4”galvanized steel conduit,
male-connector at one end, female-connector at the other end. Length: ZPJ-10P20=19.32’ / ZPJ-10P12= 11.45’ / ZPJ-10P06=5.51’ / ZPJ-10P03=3.41’

3-pole jumpers: 3*12 AWG wire, 9/16” galvanized steel conduit, male & female connector.

Raised Floor Power Box: with 6’ extender, 9/16” galvanized steel conduit, male connector.
(1) SE403EX: 20A 125V one duplex-sockets (2) SE60EX: 20A 125V two duplex-sockets

Wall-mount receptacles: with 6’ extender, 9/16” galvanized steel conduit, male connector.
(1) SE403DX: 20A 125V, one duplex-socket,
(2) SE403DX-USB: 20A 125V, one duplex-sockets, 2 USB type A.

Power Splitter (ZPS402): male-connector as head, 2 female-connector as tail as power splitter.
UL listed components and system
all main components such as terminal block, copper wire, conduit, fitting, are UL listed and supplied by UL listed manufacturers.
Warranty 5 years limited warranty.